Zieus, Solar Hybrid PCU is an integrated system consisting of a solar charge controller, inverter and a Grid charger. It provides the facility to charge the battery bank through either a Solar or Grid/DG set. The PCU continuously monitors the state of battery voltage, solar power output and the load. Due to constant usage of power, if the battery voltage goes below a set level, the PCU will automatically transfer the load to the Grid/DG power and also charge simultaneously. Once the batteries are charged to the preset level, the Zieus Solar Power Conditioning unit cuts off the Grid/DG Power from the system and restores it to feeding the loads from the battery bank while also returning to charging the battery from the available solar power. The PCU always gives preference to the solar power and will use Grid/DG power only when the solar power / battery charger is unable to meet the load requirement.


  • Load sharing between solar and Grid.
  • 100 % Utilization of solar power using Power sharing MPPT Converter and solar PCU.
  • Industrial Grade IGBT inverter with complete Galvanic Isolation (Single phase output and three phase output -Three phase single Delta Star Transformer)
  • High Efficiency Temperature compensated flat cum boost charger for extended battery life.
  • Parallel operation for Solar and Grid.
  • Solar PCU module utilizes the entire power available from solar and in the event of short-fall in power availability from solar the mains power is drawn to compensate the deficit of power.
  • Power sharing in PCU for catering to the load can be configured as per our requirement. Example Solar primary source and secondary for grid third for Battery.
Capacity
Hybrid PCU Rating(KW) 3.5kw | 5kw | 7.5kw | 10kw | 15kw | 20kw | 25kw | 30kw | 45kw | 60kw | 75kw | 100kw | 200kw | 300kw
MPPT Power Sharing Converter IGBT Based Active Double Boost Maximum power Tracking Converter
3kw to 100kw
Panel DC 120 VDC to 800 VDC
Input ( Rectifier ) Active power factor correction > 0.99 with IGBT Based with power sharing configuration.
Nominal AC Input Voltage 1,3 Phase 400 V AC + Neutral + Earth
Line Low / High Range 380 V AC - 480 V AC
Frequency Range 45Hz to 55Hz
Power factor ≥ 0.99 @ full load
Efficient (AC - DC) ≥ 97% @ full load
Current Harmonics Distortion (ITHD) < 4% @ full load
Solar Power / Solar Panel
Solar panel voltage@ max -Vamp (V) 260w/36vdc. 280w/36vdc. 300w/36vdc. 350w/36vdc
Solar panel current @max-Imp ( I ) 7.22A / 7.77A / 8.33A / 9.72A
Solar panel power 260 w / 280 w / 300 w /350w any one series parallel combination
Output (PCU) PWM Technology with IGBT Based / H bridge. open delta/ star transformer
Voltage Single phase 230, 3 Phase 380 -400-415 VAC + Neutral
Voltage Regulation ± 1%
Frequency (Free running) 50Hz ± 0.1%
Frequency Regulation ± 1%
Phase displacement ± 1% for 0 to 100% Unbalanced load
Frequency displacement ± 1% for 0 to 100% Unbalanced load
Dynamic stability ± 2% in 5ms
Output waveform Pure sine wave
Harmonic Distortion(THD) < 3% (100% Linear Load) / ≤ 5% (100% Non-Linear Load)
Power factor 0.8 Lag to unity
Crest factor 3 : 1
Efficiency (DC-AC) ≥ 91.6%
Battery
Battery type Sealed Maintenance free lead acid, Lead acid Tubular
Battery Rating 12 V DC / 12 AH to 150 AH any rating
Battery Voltage 3.5kw / 5kw/ 7.5kw / 10kw / 15kw – 96V-240 VDC to 360 VDC
15kw / 20kw / 25w/ 30kw /
45kw / 60kw / 75kw / 100kw / 200KW / 300KW – 360 VDC
Charger Temperature compensated float cum boost charger for -7Ams to 15Amps. Above 15 Amps on request
Communication Interface
Standard NA
SNMP interface NA
GSM Communication with PCU NA
General
Operating Temperature 0 Deg to 40 Deg. C
Humidity 20% to 95%
Noise Level < 55 dB @ 1 Meter
indication LED Mains On, PCU On, PCU On Battery, Load On PCU, Load On Battery, Faulty condition, Over Temperature
LCD Display Input Voltage R, Y, B Input current R,Y,B Input Power R,Y,B Input Frequency, Output Voltage R,Y,B Output current R,Y,B Output Power R,Y,B Output Frequency, Battery Voltage
Audible Alarm Mains Failure Alarm, Low Battery pre Alarm, Over Load, PCU Over Current
PCU Protection Advanced Electronic protection for input over voltage, under voltage, device safety backed with MCBs, semiconductor fuse, soft start feature for rectifier and PCU converter, battery current limiting protection, built in over load protection, IGBT short circuit protection for rectifier and inverter
Standards IEEE-519
Dimension XXXX
Weight XXXX